XM3.1-915-HP
Power Supply
 
 

Alarms
 

Battery
 

Power Supply
Model ALPHA/XM3.1-915-HP
Firmware V1.02.0
Major Alarm OK
Minor Alarm OK
Operational Mode Line
Charger Mode Rest
Tamper Closed
Power Supply Language English
Power Supply Priority Normal
Input
AC Line Mode OK
Voltage 121.86 V
Current 4.83 A
Power 545 W
Frequency 60 Hz
Tap Status Buck tap
Frequency Range 3.00 Hz
Current Limit 17.00 A
Input Power Consumption 11,792 Wh
Output
Voltage 85.94 V
Power 460 W
Apparent Power 528.53 VA
Frequency 60.03 Hz
Percent Load 41.00 %
Output Setting 90 V
Output Regulation Coarse override
Over-current Tolerance 3.000 sec
Retry Delay 60 sec
Retry Limit 20
Active Drop Alarm OK
Active Drop Threshold 50 W
Current 6.15 A
Inverter
Inverter Status Off
End of Discharge Type String
End of Discharge Level 1.75 V/cell
Reduced Peak Mode Disable
Total Standby Events 86
Time Since Last Standby Event 431d 7h:41m
Time in Last Standby Event 0d 0h:01m
Total Time in Standby 680 min
Standby Events Since Reset 25
Time in Standby Since Reset 351 min
Time Since Reset 896 day(s)
Total Run Time 896 day(s)
Transformer Run Time 896 day(s)
Total Downtime 3d 23h:31m
Oil Cap Lifespan Consumed 38.1 %
Self Test
Deep Discharge Cycle Timed
Test Countdown 2 day(s)
Test Duration 10 min
Test Interval 30 day(s)
Test Inhibit No

 